Current Transformer Accuracy Class as per IEC 61869-2

Current transformer Accuracy class is highest permissible percentage error at rated current for that accuracy class, as per IEC 61869-2 and IS 2705.
Current transformer Accuracy class is highest permissible percentage error at rated current for that accuracy class, as per IEC 61869-2 and IS 2705.
Accuracy
Class
Allowed Error
at 1% of
Rated Current
Allowed Error
at 5 % of
Rated Current
Allowed Error
at 20 % of
Rated Current
Allowed Error
at 100 % of
Rated Current
Allowed Error
at 120 % of
Rated Current
Class 13 %1.5 %1 %1 %
Class 0.51.5 %0.75 %0.5 %0.5 %
Class 0.5s1.5 %0.75 %0.5 %0.5 %0.5 %
Class 0.20.75 %0.35 %0.2 %0.2 %
Class 0.2s0.75 %0.35 %0.2 %0.2 %0.2 %
Class 0.10.4 %0.2 %0.1 %0.1 %
Current Transformer Accuracy Class

Energy Meter or Load Manager Accuracy is defined in IEC 62053.

Accuracy of Energy Measurement is addition of all the components used for measurement, that is CT and Meter both, which is called System Accuracy.
Related Articles:

    What is Energy Control Program ?

    Energy Control Program makes sure that Equipment is isolated from energy source and made inoperative before planned Service/Maintenance.

    What causes arc flash?

    An arc flash causes a very loud sound created by quickly-moving air, or a sound wave, that can reach 140 decibels at a distance of

    Factors affecting short circuit fault

    Short-Circuit fault allows the current to flow through unintended path with very low impedance, which results into excessive current flow through the path.

    How to do Hot Dip Galvanization ?

    Galvanization is the process of applying Zinc coating on Steel to prevent Corrosion. In Hot dip Galvanization, Fabrication is submerged in Molten Zinc.