What are Utilization categories A and B, for Circuit Breakers ?

Circuit Breaker with Short Time withstand Icw capacity are Calassified as Category B (eg. ACB), and without Icw are Category A (eg. MCCB, MCB).

Utilization categories A and B in Circuit Breaker classification.

According to IEC 60947-2, Utilization category of a circuit breaker shall be stated with reference to whether or not it is specifically intended for selectivity by means of an intentional time delay with respect to other circuit breakers in series on the load side under short-circuits conditions. The utilization category of a circuit-breaker shall be stated with reference to whether or not it is specifically intended for selectivity by means of an intentional time delay with respect to other circuit-breakers in series on the load side, under short-circuit conditions.

Circuit Breaker with Short Time withstand Icw capacity are Calassified as Category B (eg. ACB), and without Icw are Category A (eg. MCCB, MCB).

Utilization category A :

  • Without an intentional short-time delay for selectivity under short-circuit condition and therefore without a short-time withstand current rating.
  • Circuit-breakers not specifically intended for selectivity under shortcircuit conditions with respect to other short-circuit protective devices in series on the load side,
  • i.e. without an intentional short-time delay provided for selectivity under short-circuit conditions, and therefore without a short-time withstand current rating.
  • eg: MCCBs, MCBs., (Some MCCBs are Cat B, with Icw)
  • Utilization Category A breakers are Current Limiting.

Utilization Category B

  • With an intentional short-time delay (which may be adjustable) provided for selectivity under short-circuit conditions.
  • Such circuit-breakers have a short-time withstand current rating.
  • Circuit-breakers specifically intended for selectivity under short-circuit conditions with respect to other short-circuit protective devices in series on the load side,
  • i.e. with an intentional short-time delay (which may be adjustable), provided for selectivity under short-circuit conditions.
  • Such circuit-breakers have a short-time withstand current rating.
  • eg: ACBs. (Some ACBs are Cat A, current limiting)
  • Utilization Category B breakers are Selective (non current limiting)
Related Articles:

    What is Arc Flash assessment?

    Arc Flash assessment determines the degree to which worker may be exposed to potential Arc Flash Hazards and what kind of PPE is required.

    Degree of Burn

    Degree of Burn is the level of depth of Burn effect on the human skin up to bones.

    DC Utilization Categories IEC 60947

    Utilization Categories indicate the type of Load and Duty Cycle of the load basis which selection of Switchgear should be done for the intended application.

    LOTO – Lockout Tagout

    LOTO – Lockout Tagout is the Physical restraint of Device as Hazardous Energy source, While doing Servicing/Maintenance.

    Let Through Energy

    I2t – Let through Energy is available thermal energy resulting from Current Flow during circuit opening. I2t (of circuit breaker) < K2S2 (of cable)