Insulation coordination for Switchgear and Assembly as per IEC 60664

Rated Impulse Voltage (Uimp) for Overvoltage category -- I, II, III, IV at various nominal Voltage (Ue) is suggested in IEC 60664.

Rated Impulse Voltage (Uimp) for Overvoltage category — I, II, III, IV at various nominal Voltage (Ue)

Nominal Voltage
Ue
Line to Neutral
Uimp for
Overvoltage
category — I
Uimp for
Overvoltage
category — II
Uimp for
Overvoltage
category — III
Uimp for
Overvoltage
category — IV
Vph – 50330 V500 V800 V1500 V
Vph – 100500 V800 V1500 V2500 V
Vph – 150800 V1500 V2500 V4000 V
Vph – 3001500 V2500 V4000 V6000 V
Vph – 6002500 V4000 V6000 V8000 V
Vph – 10004000 V6000 V8000 V12000 V
Insulation coordination

Min Impulse Withstand Voltage for Rated Operatonal Voltage of 230VAC

Impulse
withstand
category
Required
Impulse
withstand voltage
Equipment
in category
Cat – I
(low impulse
voltage)
1.5 KVSensitive electronic equipment –
Eg: TV, Laptop, Electronic Equipments
Cat – II
(normal impulse
voltage)
2.5 KVDomestic appliances –
Eg : Washing Machine, Fridge,
Cat – III
(high impulse
voltage)
4 KVMain Distribution Boards
Cat – IV
(very high impulse
voltage)
6 KVNear the Energy Meter
Min Impulse Withstand Voltage for Rated Operatonal Voltage of 230VAC

Let Through Energy

I2t – Let through Energy is available thermal energy resulting from Current Flow during circuit opening. I2t (of circuit breaker) < K2S2 (of cable)

AC Utilization Categories IEC 60947

Utilization Categories indicate the type of Load and Duty Cycle of the load basis which selection of Switchgear should be done for the intended application.