Motor Contribution in Short Circuit Fault

Motor contribution is the Current feed back by Motor, due to rotating magnetic fied in rotor, into System during short circuit condition.
Fault Current Contribution of Motor is Signifacant in Short Circuit Calculations, and its calculations are defined in IEC 60900 and ANSI C37.010

During Short Circuit utility stable supply dips and Rotor continues to rotate due to inertia, at this time Rotating magnetic field in the rotor tries to support reduced voltage and there by becomes Power Source. Hence during this time reaction of Motor will be similar to Generator. At this time Motor will have Sub transient of 20 to 25%.

Motor Contribution for Short Circuit Fault :
  • Asynchronous Induction Motor : 4 x Ifla-motor
  • Induction Motor with Standard VFD : 0
  • Induction Motor with AFE VFD : 2 x Ifla-motor

Prospective Short Circuit Current Trafo + Motor Contribution

Transformer
Parameters
2500
KVA
2000
KVA
1600
KVA
1250
KVA
1000
KVA
630
KVA
500
KVA
400
KVA
315
KVA
250
KVA
Line Voltage
Volts
433433433433433433433433433433
Impedance
% z
6.256.256.25554.54.54.54.54.5
Trafo FLA
Amps
33342667213316671333840667533420333
Trafo
Isc KA
53.3
KA
42.7
KA
34.1
KA
33.3
KA
26.7
KA
18.7
KA
14.8
KA
11.9
KA
9.3
KA
7.4
KA
Motor Contribution KA
25% Motor Load
without VFD
3.3
KA
2.7
KA
2.1
KA
1.7
KA
1.3
KA
0.8
KA
0.7
KA
0.5
KA
0.4
KA
0.3
KA
Motor Contribution KA
25% Motor Load
with Standard VFD
0000000000
Motor Contribution KA
10% Motor Load
with AFE VFD
0.7
KA
0.5
KA
0.4
KA
0.3
KA
0.3
KA
0.2
KA
0.1
KA
0.1
KA
0.1
KA
0.1
KA
Total
Motor Contribution KA
4.0
KA
3.2
KA
2.6
KA
2.0
KA
1.6
KA
1.0
KA
0.8
KA
0.6
KA
0.5
KA
0.4
KA
Highest
SC Fault
KA
57 KA46 KA37 KA35 KA28 KA20 KA16 KA12 KA10 KA8 KA
Prospective Short Circuit Current Trafo + Motor Contribution

Motor Contribution will be upto 4 cycles incase of Induction Asynchronous Motors. Whereas it will be upto 8 cycles for synchronous Motors.

Now a days it is now Standard Practice to use VFD for Motor, In this case VFD-Motor set will not contribute for Short Circuit Current.

However, when the VFD is with AFE – Active Front End, i.e Regenerative, it will contribute for short Circuit Current.

Prospective Short Circuit Current Generator + Motor Contribution

Generator
Parameters
2500
KVA
2000
KVA
1500
KVA
1000
KVA
750
KVA
500
KVA
400
KVA
250
KVA
Line Voltage
Volts
415415415415415415415415
Sub Transient
X”d
1817171615111010
Genset FLA
Amps
34782782208713911043696556348
Genset
Isc KA
19.3
KA
16.4
KA
12.3
KA
8.7
KA
7.0
KA
6.3
KA
5.6
KA
3.5
KA
Motor Contribution KA
25% Motor Load
without VFD
3.5
KA
2.8
KA
2.1
KA
1.4
KA
1.0
KA
0.7
KA
0.6
KA
0.3
KA
Motor Contribution KA
25% Motor Load
with Standard VFD
00000000
Motor Contribution KA
10% Motor Load
with AFE VFD
0.7
KA
0.6
KA
0.4
KA
0.3
KA
0.2
KA
0.1
KA
0.1
KA
0.1
KA
Total
Motor Contribution KA
4.2
KA
3.3
KA
2.5
KA
1.7
KA
1.3
KA
0.8
KA
0.7
KA
0.4
KA
Highest
SC Fault
KA
23 KA20 KA15 KA10 KA8 KA7 KA6 KA4 KA
Prospective Short Circuit Current Generator + Motor Contribution
What is Motor Contribution in Short Circuit Fault?

Motor contribution is the Current feedback by Motor into System during short Circuit condition. Due to Rotor inertia, it keeps on running for some time, even if there is a deep in supply voltage, and now motor becomes source and feeds back in to network. This Amount of Current is dependent on the Motor Impedance. Duration of this condition is normally up to 4 to 5 Cycles.

What are very conservative assumption to calculate Short Circuit Fault in System ?

To calculate highest vault of Short Circuit Fault at the main PCC Level, If we consider Infinite utility source to Transformer primary Plus 4 times Full load current of Motor as Motor Contribution to short Circuit fault, this will be highest possible Short Circuit Current that system will be able to feed for a Short Circuit Fault at any point in the electrical network.

Related Articles: