IP Degree of protection IEC 60529

Protection degree provided by Assembly against ingress of solid foreign particals and liquid is indicated by the IP code.

Protection degree provided by Assembly against ingress of solid foreign particals and liquid is indicated by the IP code according to IEC 60529.

Ingress of
Solids
Ingress of
liquids
Against access to
hazardous part
0 : Non protected 0 : Non protected Non protected
1 : ≥ 50 mm diameter 1 : Vertically dripping Back of hand
2 : ≥ 12.5 mm diameter 2 : Dripping from 15° angle Finger
3 : ≥ 2.5 mm diameter 3 : Spraying from 60° angle tool
4 : ≥ 1.0 mm diameter 4 : Splashing from any angle Wire
5 : Dust protected 5 : Jetting from any angle Wire
6 : Dust tight 6 : Powerful jetting from any angle Wire
  7 : Temporary immersion, ≤ 1 meter depth  
  8 : Continuous immersion, ≥ 1 meter depth  
  9 : High pressure water  
     
     
IP Degree of protection IEC 60529

Additional letter IPxxY (Y=ABCD), for Protection against direct contact of foreign object resulting from the access to hazardous current carrying parts.

Terms Term Description
IP xx A Protection against access with back of hand, 50 mm.
IP xx B Protection against access with 12 mm diameter finger.
IP xx C Protection against access with 2.5 mm diameter tool.
IP xx D Protection against access with 1 mm diameter wire.
   
What is IP degree Protection ?

IP – Ingress Protection, is classification of Ingress Protection of Switchboard Assembly against sealing effectiveness of intrusion from foreign bodies like dust, wires, tools, fingre and Liquids.

 