Generator Prospective Short Circuit Current

Highest Prospective Short Circuit Current which a typical Generator can feed in case of of Short Circuit fault for Individual and Multiple Generators.
Highest Prospective Short Circuit Current Isc which a Generator can feed in case of Short Circuit fault is as given Bellow:
Generator
Parameters
2500
KVA
2000
KVA
1500
KVA
1000
KVA
900
KVA
750
KVA
625
KVA
600
KVA
500
KVA
400
KVA
380
KVA
320
KVA
250
KVA
Line Voltage
Volts
415415415415415415415415415415415415415
Sub Transient X”d18171716161514121110101010
Genset Full Load
Current FLA Amps
347827822087139112521043870835696556529445348
Genset
Isc KA
19.316.412.38.77.87.06.27.06.35.65.34.53.5
Short Circuit Ratio0.430.430.430.430.420.490.420.430.480.430.420.550.55
Short Circuit
withstand current
for 5 to 10 Sec
10434834762614174375631302609250420871669158613361043
Genset Main
Circuit Breaker
In Amps
40003200250020001600125010001000800630630630400
CB In Panel Rating
At 45*C Ambient
Room Temperate
350029002300180015001100900900700550550550365
Generator Prospective Short Circuit Current Isc
Prospective Short Circuit Current of Multiple Generators connected at Synchronising panel is Cumulative Short Circuit KA of all individual Generators.
Generator Prospective Short Circuit current compared to Similar KVA rating of Transformer, is typically 5 times weaker.
What is Short Circuit?

Short Circuit is a fault which allows the current to flow through its unintended path with very low impedance, which results into excessive current flow through the path.

What is Sub Transient Reactance of Generator ?

It is the Reactance of Sub Transient period, which is immediately after short circuit on the generator, this period lasts for typically 10 mSec to 20 mSec. Typical Sub Transient Impedance is 10% to 20%.

What is Transient Reactance of Generator?

It is the Reactance of Transient period which is immediately after Sub Transient period of the generator, this Reactance period lasts till the short circuit fault settles, this settled value is typically less then rated current of Generator. Normally Transient Impedance is 15% to 25% and it lasts from 100 mSec to 500 mSec.

What is Short Circuit ratio of Generator ?

Short Circuit ratio of Generator is the ratio of field current required to produce rated voltage on No Load to field current required to produce rated voltage on Short Circuit condition.

What is the Relation of Short Circuit Ratio – SCR with Reactance – Xd of Generator ?

With Higher SCR, Xd will be low, Result will be Good Voltage Regulation and Increase in Alternator stablity.
With Lower SCR, Xd will be High, Result will be low value of Short Circuit Current.

What is Generator Stablity ?

It is the ability or Resilience of Generator to return to Steady State condition after observing disturbance.

How to calculate Synchronizing Panel Total Short Circuit ?

Total Short Circuit current on the HBB of Synchronizing Panel is Cumulative sum of all individual Generator Short Circuit Currents.

Short Circuit
Impedance

Typical
reactance (%)
Short Circuit Current
Isc multiple of In

Typical
time
Subtransient
Phase X”d
10% to 20%Isc = 6xIn to 12xIn10 mSec to 20 mSec
Transient Phase
X’d
15% to 25%Isc = 1.5xIn to 2xIn100 mSec to 500 mSec
Steady state
Phase Xd
200% to 300%Isc = 0.5xIn> 500 mil Sec
Generator short circuit impedance for various phase