Current Transformer Phase Displacement as per IEC 61869-2

In Practice there wiill always difference in phase displacement between primary and secondary currents, Allowed limits are defined in IEC 61869-2.
For a Perfect CT, difference in phase between the primary and secondary currents, the positive direction of the primary and secondary currents, will be zero. However, in Practice its not possible, hence, Allowed phase displacement at various % of rated currents are defined in IEC 61869-2.

Phase displacement or Phase sift is immaterial for Current measurement, however its very important factor for Power, Energy, Power Factor and Power Quality Measurements.

Accuracy
Class
Allowed Phase
Displacement
at 1 % of
Rated Current
Allowed Phase
Displacement
at 5 % of
Rated Current
Allowed Phase
Displacement
at 20 % of
Rated Current
Allowed Phase
Displacement
at 100 % of
Rated Current
Allowed Phase
Displacement
at 120 % of
Rated Current
Class
1
Minutes — 180
CentiRadian — 5.4
Minutes — 90
CentiRadian — 2.7
Minutes — 60
CentiRadian — 1.8
Minutes — 60
CentiRadian — 1.8
Class
0.5
Minutes — 90
CentiRadian — 2.7
Minutes — 45
CentiRadian — 1.35
Minutes — 30
CentiRadian — 0.9
Minutes — 30
CentiRadian — 0.9
Class
0.5s
Minutes — 90
CentiRadian — 2.7
Minutes — 45
CentiRadian — 1.35
Minutes — 30
CentiRadian — 0.9
Minutes — 30
CentiRadian — 0.9
Minutes — 30
CentiRadian — 0.9
Class
0.2
Minutes — 30
CentiRadian — 0.9
Minutes — 15
CentiRadian — 0.45
Minutes — 10
CentiRadian — 0.3
Minutes — 10
CentiRadian — 0.3
Class
0.2s
Minutes — 30
CentiRadian — 0.9
Minutes — 15
CentiRadian — 0.45
Minutes — 10
CentiRadian — 0.3
Minutes — 10
CentiRadian — 0.3
Minutes — 10
CentiRadian — 0.3
Class
0.1
Minutes — 15
CentiRadian — 0.45
Minutes — 8
CentiRadian — 0.24
Minutes — 5
CentiRadian — 0.15
Minutes — 5
CentiRadian — 0.15
Current Transformer Phase Displacement
Related Articles:

    DC Utilization Categories IEC 60947

    Utilization Categories indicate the type of Load and Duty Cycle of the load basis which selection of Switchgear should be done for the intended application.

    Arc Flash Hazard Risk Category

    HRC – Hazard Risk Category is determined by amount of Incident Energy released upto defined boundary from the source of Arc Flash Point.