IEEE 519-2014 Current distortion limits

For Electrical Network with non linear loads, Current Distortion limits are defined in IEEE 519. To ensure Quality Power Supply to Assets, Mitigate !!
Isc / IL3 <= h < 1111 <= h 1717 <= h < 2323 <= h < 3535<= h < 50TDD
< 204.02.01.50.60.35.0
20 < 507.03.52.51.00.58.0
50 < 10010.04.54.01.50.712.0
100 < 100012.05.55.02.01.015.0
> 100015.07.06.02.51.420.0
IEEE 519-2014 Current distortion limits