IEEE 519-2014 Current distortion limits

For Electrical Network with non linear loads, Current Distortion limits are defined in IEEE 519. To ensure Quality Power Supply to Assets, Mitigate !!
Isc / IL3 <= h < 1111 <= h 1717 <= h < 2323 <= h < 3535<= h < 50TDD
< 204.02.01.50.60.35.0
20 < 507.03.52.51.00.58.0
50 < 10010.04.54.01.50.712.0
100 < 100012.05.55.02.01.015.0
> 100015.07.06.02.51.420.0
IEEE 519-2014 Current distortion limits
Related Articles:

    When can Arc Flash occur ?

    Arc Flash occurs when insulation or isolation between electrified conductors is breached or can no longer withstand the applied voltage.

    Burns caused by Arc Flash

    Degree of severity of burns is based on size and depth of the burn on human body. Fire, steam, Radiation, chemicals, Electric Arc, can cause burns.