Effects of Arc Blast overpressure on Structure and Worker

Arc Blast overpressure is created due to blasting molten metal and expanding plasma inside of the ASSEMBLY.
Due to Arc Fault, the massive energy Released – Arc Blast is created due to blasting molten metal and expanding plasma inside of the ASSEMBLY with extraordinary force, which Damages the Assembly and throws not only metals pats, doors but can also blow worker away from the Arc. This Blow of worker may be more severe than Arc Burn.
Overpressure Wind Speed Effects on Structures Effects on Human Body
1 psi 60 kmph Following may Break/Shatter :
Panel glass doors,
LCD Glass of Meters or Switchgear,
Panel Room Window glass
Minor injuries to human body
may happen due to Glass
break/shatter.
2 psi 110 kmph Moderate damage to
Switchboard Assembly and
Panel Room may happen.
Major injuries to Human body,
due to flying debris may happen.
3 psi 160 kmph Switchboard Assembly may Collapse
And Panel Room Structure
may also get collapse.
Major injuries to Human body
will be obvious, and fatalities
are likely.
5 psi 260 kmph Panel Room and
Building Structure may Collapse.
Fatalities are likely in the Panel room.
10 psi 470 kmph Reinforced concrete building
may get damaged.
Fatalities are likely beyond Panel room,
near by room and Structures.
20 psi 800 kmph Heavily built Reinforced concrete Building
may get demolished.
Fatalities are likely in the entire
Building Structure.
Effects of Arc Blast overpressure on Structure and Human Body
What is “psi” in Pressure?

Psi is pounds of force per square inch area.
1 pound = 0.454 kg
1 inch = 2.54cm
1 psi = Pressure due to Weight of 1 pound/0.454 kg on 1 inch2 / 2.54 cm2 of area.
1 psi = 6894 N/m2
1 psi = 0.068 atmosphere

What is Arc Blast?

Arc Blast is the supersonic shockwave produced when the uncontrolled Arc vaporizes the metal conductors.
The massive energy released in the Arc fault rapidly vaporizes the metal conductors involved, blasting molten metal and expanding plasma inside of the ASSEMBLY with extraordinary force, which Damages the Assembly and throws metals pats, doors, this can be big damage for Asset Protection and Employee Protection.

What is color of Arc Blast Smoke ?

After the Arc Blast, Metal vapors while cooling down becomes oxide of the metal of the arc, during this minute particles appars like smoke.
Color of this Metal Vapor/Smoke will be as follows :
Iron: Black.
Copper: Black.
Aluminum : Grey.

Related Articles:

    What is Electrical Insulating Materials ?

    Nonconducting material that provides electric isolation of two parts at different voltages.
    It must have an electrical resistivity and a dielectric strength sufficiently high for the given application.
    The secondary requirements relate to thermal and mechanical properties.

    When can Arc Flash occur ?

    Arc Flash occurs when insulation or isolation between electrified conductors is breached or can no longer withstand the applied voltage.

    What is Ambient Air Temperature?

    Reference Ambient Air Temperature is one third (1/3) of sum of Maximum Air Temperature “Current + Daily Average + Annual Average + 10°C”. As per IS 9676.

    Fire Classification

    Fire Classification basis Material Involved in Fire and Essential Extinguiser Effect required for Fire Suppression.